Protection Against Electric Shock - Eaton PowerXL DC1 20 Series Installation Manual

Variable frequency drives
Table of Contents

Advertisement

3 Installation

3.9 Protection against electric shock

3.9 Protection against electric shock
120
Ensuring protection against electric shock when using DC1...E1
variable frequency drives, as per IEC/EN 61800-5-1
Manufacturer's declaration for the initial verification as per
IEC/HD 60364-6 (DIN VDE 0100-600 (VDE 0100-600)) and for periodic
testing as per EN 50110-1 (DIN VDE 0105-100 (VDE 0105-100))
Fault protection in accordance with IEC/HD 60364-4-41 (DIN VDE 0100-410
(VDE 0100-410)) for the output-side circuits of the aforementioned apparatus
is guaranteed provided that the following requirements are met:
The installation instructions in this documentation have been observed.
The applicable standards in the IEC/HD 60364 (DIN VDE 0100
(VDE 0100) series have been observed.
The continuity of all associated protective conductors and equipotential
bonding conductors, including the corresponding connection points, has
been ensured.
Provided that the above requirements are met, the aforementioned
apparatus meets the requirements in IEC/HD 60364-4-41 (DIN VDE 0100-410
(VDE 0100-410):2007-06, section 411.3.2.5) when using the "automatic
power supply shutdown" protective measure.
The note is based on the following information:
In the event of a short-circuit with negligible impedance to a protective
conductor or to earth, the aforementioned apparatus will reduce the output
voltage within a time as required in table 41.1 or within 5 seconds –
depending on the applicable scenario – as per IEC/HD 60364-41 (DIN VDE
0100-410; VDE 0100-410):2007-06).
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents