Table 21: Selector switch for DC1-...A6S...
0
0
FWD
REV
FWD
FWD
FWD
FWD
Run in Hand
Run in PI Control
Run in PI Control
Run in Auto
Run in Auto
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
Parameter
P-12
P-15
FWD
0
0
0
5, 7
0
1
0
6, 8
0
4
5
1
5
0, 2, 4, 5,
8, 9, 10,
11, 12
3
6
3
3
4.4 Commissioning with local controls
Description
Factory Default Configuration
Run Forward or Reverse with speed controlled from
the local POT
Run forward with speed controlled form the local
POT
Run Reverse – Disabled
Run Forward with speed controlled from the local
POT
Preset Speed 1 provides a 'Jog' Speed set in P-20
Run Forward or Reverse with speed controlled from
the local POT
Run in Hand – Speed controlled from the local POT
Run in Auto – Speed controlled using Analog input 2
e.g. from PLC with 4-20mA signal.
In Speed Control the speed is controlled from the
local POT
In PI Control, Local POT controls PI set point.
In Preset Speed Control, P-20 sets the Preset Speed
In PI Control, POT can control the PI set point
(P-44 = 1).
Hand – Speed controlled from the local POT
Auto – Speed Reference from Modbus
Hand – Speed reference from Preset Speed 1 (P-20)
Auto – Speed Reference from Modbus
4 Operational
127