Dxc-Ext-2Ro1Ao Output Expansion - Eaton PowerXL DC1 20 Series Installation Manual

Variable frequency drives
Table of Contents

Advertisement

7 Accessories
7.1 Device-specific accessories

7.1.3 DXC-EXT-2RO1AO output expansion

186
Figure 94:
DXC-EXT-2RO1AO
Expansion module DXC-EXT-2RO1AO was developed with HVAC
applications in mind. It can switch the "Drive running" and "Shutdown due
to fault" messages with two separate relays (K1, K2).
Table 50: Specific technical data DXC-EXT-2RO1AO
Technical data
Output switching voltage
K1 (control signal terminals 12, 13)
K2 (control signal terminals 10, 11)
AO
Relay switching current
K1 (control signal terminals 12, 13)
K2 (control signal terminals 10, 11)
AO
Operating Temperature
Degree of protection (without the connection
pins being covered by the DC1's control signal
terminal block)
For detailed instructions on how to install the module, please
refer to instruction leaflet IL04012014Z.
NOTICE
Internal relay K1 is looped with the expansion module, meaning
it can only conduct a lower current (≦ 1 A).
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
Unit
Value
V
250 AC / 230 DC
V
250 AC / 220 DC
V
0 - 10 DC
A
≦ 1
A
≦ 1
mA
< 20
°C
-10 - +50
IP00