Dc1-34 - Eaton PowerXL DC1 20 Series Installation Manual

Variable frequency drives
Table of Contents

Advertisement

Size
Rated operational current
Overload current for 60 s every 600 s
Overload current for 3.75 s every 600 s
Apparent power at rated operation
400 V
Apparent power at rated operation
480 V
Assigned motor power
at 400 V, 50 Hz
at 460 V, 60 Hz
Power side (primary side):
Number of phases
Rated operating voltage
Input current (phase current)
Minimum braking resistance
Switching frequency (pulse frequency)
Default Setting
Setting range
Voltage Boost (U
/U
)
Boost
LN
Default Setting
Max Value
Maximum leakage current to earth
(touch current), at U
: 400 V, without
LN
motor
Efficiency
Heat dissipation
At I
(150 %)
e
During no-load running, standby
(locked, without fan)
Fan
Size
1) Not with IP66 degree of protection
DC1-34...device series
Continue
Symbol
Unit
014
I
A
14
e
i
A
21
l
i
A
24.5
l
S
kVA
9.67
S
kVA
11.64
P
kW
5.5
P
HP
7.5
3
U
V
380 V - 10 % - 480 V + 10 %, 50/60 Hz
LN
342 - 528 V ±0 %, 48 - 62 Hz ±0 %
I
A
17.2
LN
R
Ω
100
B
f
kHz
8
PWM
f
kHz
4 - 24
PWM
%
2
%
15
I
mA
12.7
Touch
η
0.96
P
W
223
V
P
W
6.42
V
1)
FS3
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
6.2 Specific rated operational data
018
024
030
18
24
30
27
36
45
31.5
42
52.5
12.47
16.63
20.76
14.96
19.95
24.91
7.5
11
15
10
15
20
3
3
3
21.2
27.5
34.2
80
50
30
8
8
8
4 - 24
4 - 24
4 - 24
2
2
2
15
15
10
12.7
12.7
12.9
0.97
0.97
0.97
304
446
607
6.42
6.52
14.6
1)
1)
FS3
FS3
FS4
6 Technical Data
039
046
39
46
58.5
69
68.25
80.5
26.99
31.83
32.39
38.20
18.5
22
25
30
3
3
44.1
51.9
22
22
8
8
4 - 24
4 - 24
1.5
1.5
10
10
12.9
12.9
0.97
0.96
728
801
14.6
14.6
FS4
FS4
155

Hide quick links: