2.10 Switching to the output side

2.10 Switching to the output side

2.10.1 Contactors

50
Typical applications for switching at the DC1 variable frequency drive's
output include:
Cases in which a bypass circuit is implemented.
Cases in which it must be possible to switch on various motors as
necessary.
Cases in which several motors are connected in parallel and need to be
switched individually.
Cases in which the motor must be de-energized quickly in the event of
an emergency switching off (safety shutdown).
When an individual motor is switched off, the inverter needs to be disabled
first (the FWD/REV enable signal must be switched off) before the contacts
(contactor, switch-disconnector) on the variable frequency drive's output side
are opened.
NOTICE
Switching off during operation in vector mode (P-60 = 0 / 2 / 3 / 4)
is not permissible and may result in damage to the switching
device and the variable frequency drive.
In cases in which the output is switched to a running motor, parameter P-33
must have a value of 1 (flying restart circuit enabled). When this condition is
met, the DC1 variable frequency drive will be automatically synchronized
with the running motor with the enable signal (FWD/REV).
The contactors on the output side of DC1 variable frequency drives need to
be sized based on utilization category AC-3 (IEC/EN 60947-4-1) for the
assigned rated motor current and the corresponding rated operating voltage.
When a motor is being switched off, the DC1 variable frequency drive's
output (inverter) must be disabled (the FWD/REV enable signal must be
switched off) before the contacts are opened.
NOTICE
Switching off during operation in vector mode (P-60 = 0 / 2 / 3 / 4)
is not permissible and may result in damage to the contactor and
the variable frequency drive.
Vacuum contactors should not be used at a variable frequency
drive's output, as they are not suitable for switching at low
frequencies.