1 DC1 device series
1.7 Selection Criteria
1.7 Selection Criteria
28
Select the variable frequency drive according to the supply voltage U
the supply system and the rated operational current of the assigned motor.
The circuit type (Δ / ) of the motor must be selected according to the
supply voltage.
The variable frequency drive's rated output current I
equal to the rated motor current.
L1/L L2/N
L3
1
2
3
4
5 6
7
8
9 10 11
U
V
W
Figure 12:Selection criteria
When selecting the drive, the following criteria must be known:
•
Mains voltage = rated operating voltage of the motor (e. g. 3~ 400 V),
•
Type of motor (e.g., three-phase asynchronous motor)
•
Rated motor current (recommended value, dependent on the circuit type
and the power supply)
•
Ambient conditions: ambient temperature, control cabinet installation
with IP20 degree of protection or direct local installation with IP66
degree of protection.
Example based on figure 12
•
Mains voltage: 3~ 400 V, 50 Hz
•
Star-connected circuit (400 V)
•
Rated operational current: 1.9 A (400 V)
Control panel installation → IP20 degree of protection
•
•
Ambient air temperature: max. 50 °C without output reduction, IP20
→ Variable frequency drive that should be selected: DC1-342D2FN-A20CE1
•
DC1-34...: 3-phase main terminal, rated operating voltage: 400 V
•
DC1-...2D2...: 2.2 A – The variable frequency drive's rated operational
current (output current) guarantees that the motor will be supplied with
the required rated operational current (1.9 A).
DC1...20... and DC1...OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
P-07
P-08
230/400 V
3.2/1.9 A
0,75 KW
cos ϕ 0.79
-1
1410 mi n
50 Hz
P-10
P-09
of
LN
must be greater than or
e