Connection Distributor Mains - Eaton CEAG DualGuard-S Mounting And Operating Instructions

Table of Contents

Advertisement

38 Connection distributor Mains

38 Connection distributor Mains
The mains power supply of the DualGuard-S 28 or
DualGuard-S 20 is provided via a modular mains connection
distributor. The distributor contains a size 00C switch-dis-
connector with a maximum connection cross-section of 50
mm2 and enables the connection of up to 6 substations to
modular size D02-E18 outgoing distribution boxes and the
associated terminals for the neutral and earth conductors.
In the case of outgoing feeders to powerful substations,
the same outgoing network distributors can also be used
in three phases (then connection of max. 2 substations).
The components are simply plugged on from the front and
securely contacted.
Name:
Assembly:
Degree of protection:
Protection class:
Ambient temperature:
Rated voltage (Mains):
Rated current (Mains):
Rated Frequency:
Maximum number of outgoing distributors
modules
Module
Terminals Connection cross-sections
Mains feed:
Terminals Connection cross-sections
Mains Distribuiton:
Ordering details
Type
Outgoing distribution module Mains
for busbar mounting
Busbar cover profile
80
Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
Data:
On busbar
IP20
I
55°C
UN = 400/230 V AC
IN = 63 A
50 or 60 Hz
6
50 mm² Rigid/flexible
16 mm² Rigid/flexible
III for Mains
Description
Incl. 3 pieces screw caps E18 and 3 pieces D02-
fuse links 25A
Cover profile in module width for clip mounting to
the bottom tray profile
Pos.
Order No.
40071347160
40071347192

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents