Configuration And Parameterization Via Gsd File; Table 55: Profibus Dp Configuration - WAGO 750-564 Manual

4ao u/i 4-channel analog output module; voltage/current for wago-i/o-system 750
Table of Contents

Advertisement

74
Commissioning
7.3

Configuration and Parameterization via GSD File

The I/O module can also be parameterized via PROFIBUS and PROFINET
device description (GSD file).
Behavior after Overwriting with WAGO-I/O-CHECK !
If WAGO-I/O-CHECK is used to overwrite a parameterization made with the
GSD file, the I/O module operates with the WAGO-I/O-CHECK settings until the
750-333 and 750-833 Fieldbus Couplers/Controllers are restarted.
After restart, the I/O module is re-parameterized via PROFIBUS using the GSD
settings.
Pos: 90 /Serie 750 (WAGO-I/O-SYSTEM)/Anhang/Konfigurieren und Parametrieren per GSD bei PROFIBUS DP und PROFINET IO 750-0652 @ 15\mod_1366809580641_6.docx @ 117978 @ 3443444 @ 1
7.3.1
4AO U/I Configuration
7.3.1.1
PROFIBUS DP Fieldbus Couplers/Controllers 750-333(/0xx-000),
750-833(/0xx-000)
If the aforementioned PROFIBUS DP fieldbus devices are used, the process
image size is configured by selecting the corresponding GSD entry.

Table 55: PROFIBUS DP Configuration

GSD Entry
Module
750-564 4AO U/I/16Bit
750-564 4AO U/I/15Bit
750-564 4AO U/I/16Bit RA
750-564 4AO U/I/15Bit RA
PFC 750-564 4AO U/I
*)
Only available with 750-833(/0xx-000)
7.3.1.2
PROFINET IO Fieldbus Couplers 750-375(/025-000), 750-377(/025-000)
If the aforementioned PROFINET IO fieldbus couplers are used, the process
image size is configured by selecting the corresponding GSD entry.
Manual
Version 1.0.0
Submodule
n/a
*)
WAGO-I/O-SYSTEM 750
750-564 4AO U/I
PA length
Data type
[Byte]
I
O
UINT16
n/a
8
INT16
{UINT8, UINT16}
12
12
{UINT8, INT16}
n/a
n/a
Inst.
4
n/a
n/a