Scaling - WAGO 750-564 Manual

4ao u/i 4-channel analog output module; voltage/current for wago-i/o-system 750
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-564 4AO U/I
Table 52: Menu Items "Channel 1" ... "Channel 4"
Parameter
Behaviour on
K-Bus timeout
User
substitute
value
*)
Factory setting
1)
Only relevant for output channels with a positive range.
2)
Only applies to output type "current"
3)
Only applies to output type "voltage"
7.1.3.3

Scaling

Under the "Scaling" menu item, you can enable and modify the user scaling for
each channel. You select the corresponding channel via the tabs in the
application area.
The manufacturer scaling can be switched on or off, but the gain and offset
values cannot be changed.
Value
Deactivated
Hold last output value
Set output to high-
*)
impedance
Set output to user
substitute value
[Input field]
With resolution of
16 Bit:
*)
0x0000
... 0xFFFF
With resolution of
15 Bit:
*)
0x0000
... 0x7FFF
With resolution of
15 Bit + VZ:
*)
0x8000 ... 0x0000
...
0x7FFF
Commissioning
Description
Behavior when the local bus watchdog is
triggered ("Local bus communication
faulty"):
No response from the channel. The output
stage retains its last output value setting.
The local bus "RUN" LED also lights up
green when local bus communication is
faulty.
The output stage retains its last output
value setting. The local bus "RUN" LED of
the channel goes out when local bus
communication is faulty.
The output stage of the channel switches
off; the output becomes high-ohm.
A specified output value (parameter: User
substitute value) is written to the output
stage. (Value setting = "process value")
Substitute value relates to the K-Bus
setting "Set output to user substitute
value."
Note: Scaling/calibration still occurs
before the output stage sets the substitute
value.
69
Manual
Version 1.0.0