Climatic Environmental Conditions; Table 12: Max. Error/Temperature Drift By Output Range; Table 13: Technical Data - Field Wiring; Table 14: Technical Data - Climatic Environmental Conditions - WAGO 750-564 Manual

4ao u/i 4-channel analog output module; voltage/current for wago-i/o-system 750
Table of Contents

Advertisement

26
Device Description

Table 12: Max. Error/Temperature Drift by Output Range

Output Ranges
0-10 V; 2-10 V; ±10 V;
0-5 V; 1-5 V; ±5 V
0-12 V; ±12 V
0-20 mA; 4-20 mA; ±20 mA; 0-10 mA;
2-10 mA; ±10 mA; 0-12 mA; ±12 mA;
0-22 mA; ±22 mA
Table 13: Technical Data ‒ Field Wiring
Wire connection
Cross section, solid wire
Cross section, fine-stranded wire
Stripped lengths
3.5.5

Climatic Environmental Conditions

Table 14: Technical Data – Climatic Environmental Conditions
Surrounding air temperature, operation 0 °C ... 55 °C
Surrounding air temperature, storage
Operating altitude
Relative humidity
Pollution degree
Protection type
Resistance to harmful substances
Maximum pollutant concentration at
relative humidity < 75 %
Special conditions
Manual
Version 1.0.0
WAGO-I/O-SYSTEM 750
Max. Error at 25 °C
[Output range end
value: %]
0.05
0.075
0.05
Push-in CAGE CLAMP
0.08 mm² ... 1.5 mm² / AWG 28 ... 16
0.25 mm² ... 1.5 mm² / AWG 22 ... 16
8 mm ... 9 mm / 0.33 in
−25 °C ... +85 °C
0 ... 2000 m;
(> 2000 m upon request)
Max. 5 % ... 95 % without condensation
2
IP20
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
SO
≤ 25 ppm
2
H
S ≤ 10 ppm
2
Ensure that additional measures for
components are taken, which are used
in an environment involving:
– dust, caustic vapors or gases
– ionizing radiation
750-564 4AO U/I
Max. Tempe-
rature Drift
[ppm/K]
25
25
50
®

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

4ao u/i

Table of Contents