Parameter
Synchronous DA
conversion
Process image
Diagnosis: Power
supply fault
Diagnosis: Wiring
error AO−
Value
Description
If synchronous conversion is switched on,
the output channels are processed, not one
*)
Off
after another, but rather synchronously.
Thus a change to all output stages of the
I/O module occurs at the same time.
Furthermore, D/A (digital-to-analog)
conversion is coupled to the local bus
On
cycle, so the output values are updated
synchronously with the local bus.
In the standard process image, the
control/status byte of the head station is
*)
Standard
hidden and thus not visible in the fieldbus
process image.
With the "Extended" setting, the
control/status byte is shown on the fieldbus
process image. Thus the diagnostic
messages in the status byte can also be
Extended
evaluated by a higher-level controller.
Note: Changing the setting causes an
automatic restart of the node, since the
process image of the head station changes.
Switches the supply voltage monitoring
Off
on/off If the supply voltage is faulty, a
corresponding error message is output in
the status byte of all channels.
*)
On
Switches the wiring error monitoring for
outputs –AOx on/off
Off
If the wiring is faulty, the outputs switch off
for about one second to prevent the
actuators on the field side from being
destroyed. After this, the system checks
*)
On
whether the error persists.