Process Values (Current); Table 33: 0-10 Ma (16-Bit Resolution); Table 34: 0-10 Ma (15-Bit Resolution); Table 35: 2-10 Ma (16-Bit Resolution) - WAGO 750-564 Manual

4ao u/i 4-channel analog output module; voltage/current for wago-i/o-system 750
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-564 4AO U/I
4.3.3

Process Values (Current)

Table 33: 0-10 mA (16-Bit Resolution)

Current Value (I)
0 mA
1 mA
2 mA
3 mA
4 mA
5 mA
6 mA
7 mA
8 mA
9 mA
10 mA

Table 34: 0-10 mA (15-Bit Resolution)

Current Value (I)
0 mA
1 mA
2 mA
3 mA
4 mA
5 mA
6 mA
7 mA
8 mA
9 mA
10 mA

Table 35: 2-10 mA (16-Bit Resolution)

Current Value (I)
2 mA
3 mA
4 mA
5 mA
6 mA
7 mA
8 mA
9 mA
10 mA
Process Value (hex)
0x0000
0x199A
0x3333
0x4CCD
0x6666
0x8000
0x9999
0xB333
0xCCCC
0xE666
0xFFFF
Process Value (hex)
0x0000
0x0CCD
0x1999
0x2666
0x3333
0x4000
0x4CCC
0x5999
0x6666
0x7332
0x7FFF
Process Value (hex)
0x0000
0x2000
0x4000
0x6000
0x8000
0x9FFF
0xBFFF
0xDFFF
0xFFFF
Process Image
Process Value (dec)
0
6554
13107
19661
26214
32768
39321
45875
52428
58982
65535
Process Value (dec)
0
3277
6553
9830
13107
16384
19660
22937
26214
29490
32767
Process Value (dec)
0
8192
16384
24576
32768
40959
49151
57343
65535
Manual
Version 1.0.0
39

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

4ao u/i

Table of Contents