Power Jumper Contacts/Field Supply; Figure 3: Power Jumper Contacts; Table 5: Legend For Figure "Power Jumper Contacts - WAGO 750-564 Manual

4ao u/i 4-channel analog output module; voltage/current for wago-i/o-system 750
Table of Contents

Advertisement

20
Device Description
3.2.2

Power Jumper Contacts/Field Supply

The I/O module 750-564 has 2 self-cleaning power jumper contacts that supply
and transmit power for the field side. The contacts on the left side of the I/O
module are designed as blade contacts and those on the right side as spring
contacts.

Figure 3: Power Jumper Contacts

Table 5: Legend for Figure "Power Jumper Contacts"

Contact
1
2
3
4
Do not exceed maximum values via power contacts!
The maximum current that can flow through the power jumper contacts is 10 A.
The power jumper contacts can be damaged and the permissible operating
temperature can be exceeded by higher current values.
When configuring the system, do not exceed the permissible maximum current
value. If there is a higher power requirement, you must use an additional supply
module to provide the field voltage.
Use supply modules for ground (earth)!
The I/O module has no power jumper contacts for receiving and transmitting the
earth potential. Use a supply module when an earth potential is needed for the
subsequent I/O modules.
Manual
Version 1.0.0
Type
Function
Spring contact Potential transmission (U
Spring contact Potential transmission (0 V) for field supply
Blade contact
Potential feed-in (0 V) for field supply
Blade contact
Potential feed-in (U
WAGO-I/O-SYSTEM 750
750-564 4AO U/I
) for field supply
v
) for field supply
v