Configuration And Parameterization With E!Cockpit; Table 54: "Calibration" Menu Item For Each Channel - WAGO 750-564 Manual

4ao u/i 4-channel analog output module; voltage/current for wago-i/o-system 750
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-564 4AO U/I

Table 54: "Calibration" Menu Item for Each Channel

Parameter
Manufacturer
calibration
User calibration
Process value
Show values in
hexadecimal
*)
Factory setting
7.2
Configuration and Parameterization with
e!COCKPIT
4
The 750-564 I/O module is supported by the e!COCKPIT commissioning tool
starting with version 1.6.1.4 – see manual "2759-0101 e!COCKPIT," Section
"Operating."
Value
Description
Offset
Indicates the offset value setting.
[Display field]
Gain
Indicates the gain value setting.
[Display field]
*)
User calibration is deactivated.
User calibration is activated.
By enabling this setting, you can also specify
the individual gain and offset values.
The offset value causes a zero offset of the
Offset
process value (shift along the Y axis).
The value entered must fall within the value
[Input Field]
range −32768 ... 32767.
The gain value is used as a gain factor applied
to the process value.
Gain
The value entered must fall within the range
from −2.0000 to 1.9999.
[Input field]
The resolution of 1/16384 has already been
taken into account for the decimal entry.
The process value (current/voltage value) for
the selected channel can be entered in this
input field.
[Input field]
Note: Confirm the input with the "Return" key on
your keyboard to write the process value to the
I/O module!
Hexadecimal representation is enabled.
*
Hexadecimal representation is disabled.
Commissioning
73
Manual
Version 1.0.0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

4ao u/i

Table of Contents