All other changes to the hardware and/or software and the non-conforming use of the components entail the exclusion of liability on part of WAGO Kon- takttechnik GmbH. Please direct any requirements pertaining to a modified and/or new hardware or software configuration directly to WAGO Kontakttechnik GmbH.
Routines or advice for efficient use of the device and software optimization. More information References on additional literature, manuals, data sheets and INTERNET pages 1.3 Number Notation Number Code Example Note Decimal normal notation Hexadecimal 0x64 C notation Binary '100' Within ', '0110.0100' Nibble separated with dots WAGO-I/O-SYSTEM 750 I/O Modules...
1.5 Scope This manual describes the Digital Output Module 750-512 2DO 230V AC 2.0 A/ Relay 2NO of the modular WAGO-I/O-SYSTEM 750. Handling, assembly and start-up are described in the manual of the Fieldbus Coupler. Therefore this documentation is valid only in the connection with the appropriate manual.
Examples of protection circuits can be seen in the section 2.1.2 "Contact Pro- tective Circuit for Relay Modules". The output module 750-512 can be used with all couplers/controllers of the WAGO-I/O-SYSTEM 750. 2.1.1.3 Display Elements...
750-512 [2DO 230V AC 2.0 A/ Relay 2NO] • 9 Schematic Diagram 2.1.1.4 Schematic Diagram DO 1 DO 2 Status AC 230 V AC 230 V DC 30 V DC 30 V 750-512 Fig. 2.1.1-3: 2-Channel Relay Output Module 750-512...
10 • 750-512 [2DO 230V AC 2.0 A/ Relay 2NO] Technical Data 2.1.1.5 Technical Data Module Specific Data Number of outputs 2 make contacts Current consumption (internal) 100 mA max. Switching voltage relay AC 250 V/DC 30 V Switching power relay 500 VA/60 W cosφ...
BV (Bureau Veritas) Conformity Marking More Information Detailed references to the approvals are listed in the document "Overview Approvals WAGO-I/O-SYSTEM 750", which You can find on the CD ROM ELECTRONICC Tools and Docs (Item-No.: 0888-0412-0001-0101) or in the Internet under: www.wago.com ->...
- attenuation only above g051214e Advantages: R/C combination - HF attenuation via power storage - suitable for A.C. voltage medium to - level-independent attenua- short Load tion Disadvantages: - exact dimensioning required g051215e - high inrush current WAGO-I/O-SYSTEM 750 I/O Modules...
Need help?