2. Commissioning
Standard mode
Compact mode

2.2.4 Configuration examples for COM PROFIBUS 3.x and 5.0

2-22
The program automatically enters the identifiers in the mask
"Configure" in standard mode.
If you wish to use compact mode:
S
Enter the identifiers in compact mode by overwriting
(summary: see Fig. 2/5).
Configuration is then completed.
Example 1:
Standard mode, highest assigned string = 2
String 0 = input module, output module/valve terminal
String 1 = input module, output module/valve terminal
String 2 = output module/valve terminal
DP identifier
Comment
0
16DX
String 0 – 2 input/output bytes
1
16DX
String 1 – 2 input/output bytes
2
16DX
String 2 – 2 output bytes
(inputs not used)
Fig. 2/12: Example 1: configuration
Example 2:
as example 1, but entry in compact mode
DP identifier
Comment
0
019
String 1 – 4 input bytes
1
037
String 2 – 6 output bytes
Fig. 2/13: Example 2: configuration
Festo P.BE-CP-FB13-E-EN en 0112e