Table of Contents

Advertisement

9.2.8 Configuration

The following instructions describe the configuration of the Rapid Link 5
modules in an EtherNet/IP network.
Connect the device to the EtherNet/IP environment.
You will need the following components to do so:
Head-end controller (PLC)
Computer (for programming and configuration purposes)
Rapid Link 5 modules
Figure 117:
Example of using Rapid Link 5
(RASP5-xxxxEIP..., RAMO5-WxxxEIP...and RAMO5-DxxxEIP...)
a Sensor (light barriers)
b RASP5
c Motor connection cable
d Mains connection on power bus
e EtherNet/IP cable
f RAMO5-D...
g RAMO5-W...
h Head-end controller (PLC)
Switch on the device (switch on the power supply L1-L3 400 V AC or
power supply 24 DC via socket M12).
Address the Rapid Link 5 modules (i.e. assign IP addresses).
(→ Section 9.2.9, Configuring the IP address, page 213)
Now configure the project.
(For information on a detailed configuration, please consult the manual
provided by the PLC's manufacturer.)
Check the LED indicators. The head-end controller must recognize the
device address and the MS and NS LEDs must light up green
(→ Section 9.2.4, LED indicators for EtherNet/IP, page 206).
Now download the project and navigate through the programming soft-
ware (such as CODESYS or Studio 5000) to RUN/Online.
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
9 Communication
9.2 EtherNet / IP
211

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rapid link ramo5Rapid link rasp5

Table of Contents