1 Rapid Link 5 system
1.6 Selection criteria
1.6 Selection criteria
28
Select a RAMO5 or RASP5 ③ device according to the supply voltage U
the supply system ① and the rated current of the assigned motor ②.
The circuit type (Δ / ) of the motor must be selected for the supply voltage
①.
The RASP5 unit's rated output current I
rated motor current. For RAMO5, current monitoring must be set to the
rated motor current.
U, I, f
③
Figure 7:
Selection criteria
When selecting the drive, the following criteria must be known:
•
Type of motor (three-phase asynchronous motor)
•
Mains voltage = rated operating voltage of the motor (e.g. 3 AC ~ 400 V),
•
Rated motor current (recommended value, dependent on the circuit type
and the supply power supply)
•
Load Torque,
•
Starting torque,
•
Ambient temperature.
ATTENTION
Do not disconnect or connect power connectors (mains, motor)
while RAMO5 and RASP5 are operational.
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
must be greater than or equal to the
e
①
②
230 / 400 V ∆ /
4.6 / 2.6
cos
1.1
kW
-1
1430
min
A
ϕ
0.81
50 Hz
of
LN