1.4 Technical data

Technical data
General
Standards
Approvals, certificates
Production quality
Protection class
Mounting position
Ambient temperature range
Operation
Storage
Set-up altitude
Humidity (IEC/EN 50178)
Vibration (IEC/EN 60068-2-6)
Amplitude
Acceleration
Mechanical shock resistance (IEC/EN
60068-2-27)
Table 2:
General rated operational data (overview)
Formula
Unit
symbol
°
C
°
C
H
m
p
%
w
Hz
Hz
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
Value
RAMO5
IEC/EN 60947-4-2
EN 50581
CE, CCC, cUL
Directive 2011/65/EU (RoHS),
ISO 9001
IP65, NEMA 12 / NEMA 12K
vertical (→ Page 82)
-10 - +40
-40 - +70
0 to 2000 above MSL with 1 % power
reduction per 100 m over 1000 m
< 95 relative humidity
non-condensing
3 - 15.8
Vibration amplitude: 0.15 mm
15.8 - 150 constant acceleration 2 g
1000 shocks per shaft,
Semisinusoidal 15 g/11 ms
1 Rapid Link 5 system
1.4 Technical data
RASP5
IEC/EN 61800-3
IEC/EN 61800-5-1
EN 50581
EN 61800-5-2
EN ISO 13849-1
EN 62061
CE, cUL
Directive 2011/65/EU (RoHS),
ISO 9001
IP65, NEMA 12 / NEMA 12K
vertical (→ Page 82)
-10 - +40 (without derating)
-40 - +70
0 to 2000 above MSL with 1 % power
reduction per 100 m over 1000 m
< 95 relative humidity
non-condensing
3 - 15.8
Vibration amplitude: 0.15 mm
15.8 - 150 constant acceleration 2 g
1000 shocks per shaft,
Semisinusoidal 15 g/11 ms
19