5.6 LED indicators

OFF/RESET
REV
OFF
PWR
AS-I
SEN I1
I1
ACT Q1
Q1
SEN I2
I2
The LEDs indicators of the RAMO5 motor control unit display the operating
states and allow problems to be quickly diagnosed.
LED
State
FWD
Off
Green
Flashing
FWD
(green)
REV
FLT
Off
Green
Data
Green flashing
Fault
AS-I
Data
Off
Green
Red
Yellow flas-
hing, red
Green,
Red flashing
Fault
Red
Red flashing
I1
Off
Green
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
Description
Clockwise rotating field of motor voltage (U–V–W)
Not actuated
enabled (RUN-Mode)
controlled:
• but inhibited by the Quick stop function of sensor inputs I1 and I2
• But blocked because when the supply voltage was switched on
(400 V or ASi), the key switch was in the MANUAL position.
→ A Reset command required.
Counterclockwise rotating field of motor voltage (W–V–U)
Only for reversing starter RAMO5-W...!
Not actuated
enabled (RUN-Mode)
controlled:
• but inhibited by the Quick stop function of sensor inputs I1 and I2
• But blocked because when the supply voltage was switched on
(400 V or ASi), the key switch was in the MANUAL position.
→ A Reset command required.
AS-Interface
ASi electronics have no supply voltage:
Check ASi connection cables
Check ASi power supply unit (head-end controller)
Communication active, normal operation
No communication:
• Head-end controller (master) in STOP mode.
• RAMO5 not entered or entered with the wrong address (ID).
• RAMO5 in Reset mode.
ASi address = 0
→ Adjust ASi address
fatal peripheral error, internal ASi error
No data exchange, communication error
Peripheral fault,
Sensor input SEN I1
• not connected
• not triggered (no input signal)
SEN I1 triggered (input signal)
5 RAMO5 motor starter
5.6 LED indicators