4.3 Manual control

RAMO5 and RASP5 Rapid Link 5 modules come with a manual controller
(local controller) as standard. This controller is made up of a key switch and,
in the case of RAMO5-W and RASP5, of a direction selector switch.
The manual control allows:
a simple commissioning,
local operation during setup and maintenance,
manual operation of a single drive unit with the overall system in
Auto mode,
secure (interlocked) manual operation within an area secured with
limit switches (→ Section 2.9, Sensor inputs, page 61).
OFF/RESET
0
Figure 73:
Key-operated switch
The key is maintained in all switch positions and can be inserted
and removed in all positions.
The key switch has three different positions.
Position
Function
Automatic
mode
Manual mode
OFF/RESET
Off
Reset
command
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
Description
Automatic operation through
Local operation, even without AS-Interface parameters.
Start enable is issued using the direction selector switch (FWD, REV) on
RAMO5-W... and RASP5 units.
On RAMO5-D... units, the start enable signal is sent using the key switch.
(Manual position).
In this position, RAMO5 and RASP5 do not execute any control commands,
regardless of the source of the control commands.
4 Operation
4.3 Manual control
119