8.4.6 Parameter group 5 (Communication)

Parameter
Designation
P5-01
RS485-0 Address
P5-02
COM Loss Timeout
P5-03
Action@Communica-
tion Loss
P5-04
FieldbusRampControl
P5-05
NETSendPZD3
P5-06
NETSendPZD4
P5-07
NETReceivePZD3
P5-08
NETReceivePZD4
Table 45:
Parameter group 5 (Communication)
Description
Unique address of the drive (keypad, OP bus)
With an active communication link, if a valid telegram is not
received by the drive within the period set with this para-
meter, the drive will react as set in P5-03.
Device reaction after "Communication Loss" occurs.
Possibilities device dependent
0: Trip
1: Ramp to stop, then trip
2: Ramp to stop only (no trip)
3: Run at preset speed 2 (P2-01)
Fieldbus Ramp Control
0: OFF. Ramps are controlled by internal drives parameters
1: ON. Ramps are controlled by the fieldbus.
Configuration of the 3rd process data word PDO-3 from the
drive to the network master during cyclic communication.
0: Motor current in A with one decimal place,
e.g. 100 ≙ 10.0 A
1: Output power in kW with two decimal places,
e.g. 400 ≙ 4.00 kW
2: Status of the sensor inputs (SEN I).
Bit 0 = status SEN II1, bit 1 = status SEN I2, etc.
3: Internal temperature. -500 - 1500 ≙ -50 - 150 °C
Configuration of the 4th process data word PDO-3 from the
drive to the network master during cyclic communication.
0: Motor current in A with one decimal place,
e.g. 100 ≙ 10.0 A
1: Output power in kW with two decimal places,
e.g. 400 ≙ 4.00 kW
2: Status of the sensor inputs (SEN I).
Bit 0 = status SEN II1, bit 1 = status SEN I2, etc.
3: Internal temperature. -500 - 1500 ≙ -50 - 150 °C
Configuration of the 3rd process data word PDI-3 from the
network master to the drive during cyclic communication.
0: reserved
1: User defined ramp times, e.g. 500 ≙ 5.00 s.
Configuration of the 4th process data word PDI-4 from the
network master to the drive during cyclic communication.
0: reserved
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
8 Parameter list
8.4 Parameter groups for RASP5
Unit
Min
Max
1
63
s
0
5.0
0
3
0
1
0
6
0
6
0
3
0
3
DS
1
2
0
0
0
1
1
0
187