5 RAMO5 motor starter
5.7 Configure specialist settings

5.7.6 Monitoring the low current limit

5.7.7 Quick stop

134
Parameter
Designation
P6-05
Action@Under-
load Motor
When set to P6-05 = 1 (= ON), an error message will be issued (FLT LED will
light up red) if a phase (L1, L2, L3) carries less than 25 % of the rated current
l
.
e
The Quick stop function is activated using parameter P5-10 and deactivated
with DQ3. The Quick stop function is enabled via DQ3 (ASi).
Parameter
Designation
P5-10
Disable
quick stop
P5-10
DQ3
Function
1
0
Quick stop ON
1
1
Quick stop OFF
0
0
None
0
1
None
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
Description
Device response (depending on device)
after "Motor underload" occurs.
0: deactivated
1: Error (shutdown)
Description
0: Quick stop via sensors deactivated.
1: Quick stop via sensors activated
(ASi signal active).
Description
Response to sensors
No response to sensors
DQ3 signals will not be transmitted
DQ3 signals will not be transmitted
Unit
Min
Max
DS
0
1
0
Unit
Min
Max
DS
0
1
0