5 RAMO5 motor starter
5.7 Configure specialist settings
5.7.4 Quick stop and interlocked Manual mode
132
RAMO5-D... DOL starter
P1-13
Configuration
Functions of SEN I1 and
SEN I2
1
No function (as supplied)
2
SEN I1 and SEN I2 stop the
motor in Auto and Manual mode
3
SEN I1 stops the motor in
Auto mode
4
SEN I1 stops the motor in
Auto and Manual mode
RAMO5-W... reversing starter
P1-13
Configuration
Functions of SEN I1 and
SEN I2
1
No function
2
SEN I1 stops the motor in both
rotation directions in Auto mode
3
SEN I1 stops the motor in the
FWD direction in Auto mode
SEN I2 stops the motor in the
REV direction in Auto mode
4
SEN I1 stops the motor in the
FWD direction in Auto and
Manual mode
SEN I2 stops the motor in the
REV direction in Auto and
Manual mode
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
Restart conditions in
Manual mode
–
Key switch reset on rising edge
–
Key-operated switch reset and
SEN I1 no longer active
on rising edge or level detection
Restart conditions in
Manual mode
–
–
–
REV: Change direction of rota-
tion to FWD for edge or level
control
FWD: from REV and loss of
SEN I1
FWD: Key switch reset and
SEN I1 no longer active for
edge control or level control
FWD: Change direction of rota-
tion to REV for edge or level
control
REV: from FWD and loss of
SEN I2 for edge control or level
control
REV: Key switch reset and
SEN I2 no longer active for
edge control or level control
Restart conditions in Auto
mode
–
Command change via ASi
Command change via ASi
Command change via ASi
Restart conditions in Auto
mode
–
Command change via ASi
Command change via ASi
Command change via ASi