2.12 Motor and application

2.12.1 Motor selection

2.12.2 Motor and circuit type

General recommendations for motor selection:
Basically, three-phase AC motors with squirrel-cage rotors and surface-
cooling (also know as three-phase asynchronous motors or standard
motors) can be connected to the output of RAMO5 and RASP5
Rapid Link modules. Other motor types, such as external-rotor motors,
slip-ring motors, reluctance motors, or synchronous or servo motors can
also be connected provided their electrical and connection characteris-
tics are the same as those of asynchronous motors and their manufactu-
rer has approved them for the application.
Only one motor with at least temperature class F (155 °C maximum
continuous temperature) should be operated on the frequency-controlled
RASP5.
Four-pole motors should preferably be selected (synchronous speed:
1500 rpm at 50 Hz or 1800 rpm at 60 Hz).
Operating conditions for S1 operation according to IEC 60034-1.
The rated current of the motor and RAMO5 or RASP5 should be identical.
The motor's stator winding can be connected in a star or delta circuit as per
the rated operational data on the name plate.
230
/ 400
V
S1
0,75
kW
1430
rpm
Figure 28:
Example of a motor ratings plate
U1
V1 W1
U1
V1 W1
W2 U2
V2
W2 U2
Figure 29:
Circuit types:
Star-connected circuit (left), delta circuit (right)
A three-phase motor with the rating plate shown in Figure 28 can only be run
in a star connection for RAMO5 (U
The rated operational current of the motor with 2 A at 400 V requires a
Rapid Link module (RAMO5 or RASP5) with a rated operational current of at
least 2 A.
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
3.5 / 2
A
cos
φ
0.79
50 Hz
V2
= 400 V).
LN
2 Engineering
2.12 Motor and application
69