Configuration File; Backup And Restore - Eaton APS3-400 Series Installation And Operation Manual

Access power solutions
Table of Contents

Advertisement

Access Power Solutions Installation Guide (APS3-400 Series)

Configuration File

The operational settings of the dc power system are stored in a configuration file loaded into the
SC200 or SC100 system controller.
The SC200 or SC100 is supplied pre-loaded with a configuration file. If this configuration file
has been customized for the site then no further configuration changes will be necessary.
Otherwise, it is important that the settings of this configuration file are checked and changed as
required for site-specific conditions. In particular, settings that may affect the performance and
life expectancy of the battery must be checked and set according to the battery manufacturer's
recommendations.
Some settings in the configuration file can be edited using the system controller's keypad (see
details on page 42), or all settings can be edited using a PC/laptop with DCTools/Web (see
details on page 44) or remotely, see Communications Options in the System Controller
Operation Handbook.

Backup and Restore

The configuration file settings in the SC200 or SC100 can be saved to (Backup) or loaded from
(Restore) a PC/laptop using DCTools/Web.
Backup and Restore can be used to:
Load a standard (master) configuration file into an SC200 or SC100 for customization.
Copy a customized configuration file from one SC200 or SC100 to others (at similar sites).
Save a copy of a customized configuration file. This is recommended in case the SC200 or
SC100 has to be replaced.
► To use DCTools for Backup and Restore
Connect to the SC200 or SC100 with DCTools. See Communications Options in the System
1
Controller Operation Handbook.
In DCTools go to File > ICE Backup/Restore and follow the prompts.
2
The saved file does not include site specific settings including Site Identity, IP Address, S3P
Address, battery characterization data.
► To use a web browser for Backup (SC200 only)
Connect to the SC200 via a web browser. For details see Ethernet Communications in the
1
System Controller Operation Handbook.
Go to Tools.
2
Select Backup Tool.
3
Select the file type:
4
System Snapshot (*.dcs): Configuration file including site specific settings.
Configuration (*.dcc): Configuration file without site specific settings - Site Identity, IP
Address, S3P Address, battery characterization data).
Click Proceed to Backup the configuration.
5
40
Copyright © 2007-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-52D
July 2010