Controlling Rasp5 Via The As-Interface - Eaton Rapid Link 5 Manual

Table of Contents

Advertisement

9 Communication
9.1 AS-Interface

9.1.13 Controlling RASP5 via the AS-Interface

Function
No controller enable
Anticlockwise rotating field (REV)
Clockwise rotating field (FWD)
No controller enable/reset
f-Fix1 (P1-12 = 10 Hz)
f-Fix2 (P2-01 = 30 Hz)
f-Fix3 (P2-02 = 40 Hz)
f-Fix4 (P2-03 = 50 Hz)
Automatic mode
No automatic mode
Accumulative error
No accumulative error
External input SEN I1
no signal
Signal available
External input SEN I2
no signal
Signal available
200
Table 50:
Controlling RASP5
Signal to RASP5
Outputs
DQ0
DQ1
0
0
0
1
1
0
1
1
The START signal or enable for the requested operating direction is
issued through DQ0 (FWD) or DQ1 (REV).
The fixed frequencies f-Fix1 to f-Fix4 (digital setpoint value memory) are
called up in binary code through outputs DQ2 and DQ3.
If DQ2 and DQ3 are not activated, the frequency set in f-Fix1 is issued.
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
Inputs
DQ2
DQ3
DI0
0
0
1
0
0
1
1
1
1
0
DI1
DI2
DI3
0
1
0
1
0
1

Hide quick links: