8 Parameter list
8.3 Parameter groups for RAMO5

8.3.3 Parameter group 2 (Extended functions)

Parameter
Designation
P2-24
Start mode
P2-26
Auto Reset Delay
P2-27
Action@Thermistorfault Motor
P2-28
Service Interval Time
P2-29
Reset ServiceIndicator
P2-30
Parameter set
P2-32
Access Key Level2
P2-33
Parameter Lock
170
Table 36:
Parameter group 2 (Extended functions)
Description
Defines the behaviour of the drive relating to the enable
sensor input and also configures the automatic restart func-
tion.
0: Edge-r : Following power on or reset, the drive will not
start if a start signal (FWD/REV) is still present. To start a
rising edge is necessary.
1: Auto-0 : Following a power on or reset, the drive will auto-
matically start if a start signal (FWD/REV) is still present.
2, ..., 9: Auto-1 to 9 : Following a trip, the drive will make up
to 9 attempts to restart at intervals set in P2-26. The drive
must be powered down to reset the counter. The number of
restart attempts are counted, and if the drive fails to start on
the final attempt, the drive will trip, and will require the user
to manually reset the fault.
Auto Reset Delay
Determines the time that will elapse between consecutive
drive reset attempts when Auto Reset is enabled in P2-24.
Device reaction after "Thermistorfault Motor" occurs.
Possibilities device dependent
Service Interval Time
Defines the number of operating hours, after which the
service indicator is shown on the display.
With P2-29 = 1 the counter is set to the value defined here.
The remaining time until the next service is indicated with
P0-22.
Reset Service Indicator
With P2-29 = 1 the counter for the remaining hours until the
next service is set to the value defined in P2-28
Reset of P2-29 to 0 is done automatically.
Restores factory parameter settings.
Defines the password which is used to get access to
extended parameter set (Level 2).
Access via parameter P1-14.
Determines whether to lock the parameters
0: OFF. All parameters can be accessed and changed
1: ON. Parameter values can be displayed, but cannot be
changed.
If a remote keypad is connected, parameters cannot be
accessed by the remote keypad if they are locked.
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
Unit
Min
Max
0
10
s
0.1
60
0
1
h
0
60000
0
1
0
1
0
65535
0
1
DS
0
0.5
1
0
0
0
101
0