6 RASP5 speed controller
6.7 Configuration of specific settings

6.7.5 Phase change

6.7.6 Motor cable monitoring

152
In RASP5, the parameter P6-08 changes the rotating field at the output from
FWD to REV. The control logic and the LED signals remain in the FWD func-
tion.
Parameters should only be changed by expert users as specified
in the manual.
Parameter
Designation
P6-08
Change Phase-
sequence Motor
Monitoring is carried out using parameter P2-27.
Parameter P2-27 is set to the value 1 in the factory setting. In position 0, the
fault message of the thermistor and motor cable monitoring is deactivated.
Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com
Description
Changes the sequence of the output
phases.
This prevents two phases of the motor
cable from having to be swapped in
case the motor runs in the wrong direc-
tion.
0: U–V–W (clockwise rotating field)
1: U–W–V (counterclockwise rotating
field)
Unit
Min
Max
0
1
DS
0