9.7.3
Digital Inputs I1:1 - I1:8 (X10)
These inputs are available only at a PMCprimo Drive3!
All digital inputs are electrically isolated through optocouplers.
9.7.3.1
Technical characteristics
•
Reference ground is EGND (terminal X10, Pin 2)
•
Logic is PLC compatible
•
HIGH level: +11..24V / 10 mA – LOW level: 0 V .. 11 V/ 0 mA
•
The inputs I1:1 to I1:4 are „fast" inputs (< 1 us) for e.g. product referencing
•
I1:1 and I1:2 will be additionally mapped to both inputs E2:7 and E2:8 (see PMCprimo
programming manual).
9.7.3.2
Fast inputs I1:1 to I1:4
These four fast inputs can be used for special functions like referencing and initialisation.
Addidional information can be found in the PMCprimo programming manual.
Page 60
Installation manual for PMCtendo DD5/PMCprimo Drive3
9 Interfaces