9.7

Digital and analog inputs and outputs

9.7.1

Analog inputs (X3)

The servo amplifier is fitted with two programmable differential inputs for analog setpoints.
AGND (X3/7) must always be joined to the GND of the controls as a ground reference.
9.7.1.1
Technical characteristics
Differential input voltage max. ± 10 V
Ground reference AGND, terminal X3/7
Input resistance 10 kΩ
Common-mode voltage range for both inputs ± 10 V
Update rate: 62,5 µs