Move_Table (0X04) - WAGO I/O SYSTEM 750 750-671 Manual

Fieldbus independent i/o modules
Table of Contents

Advertisement

166 • Reference Commands for Move Mode
Setpoint commands
3.2.4.1.3

MOVE_TABLE (0x04)

Starts a positioning process. This command immediately deletes the
"On_Target" bit and sets that bit when the target position is reached. This
command is accepted only when the last positioning process has been
completed and the "On_Target" bit has been set. This command reads the
target position from the specified location in a separate position table. The
acceleration and velocity specified by SET_ACC (0x22) and
SET_VELOCITY (0x25) are used for positioning commands.
Byte
MB0
MB1
MB2
MB3
MB4
MB5
SRC
Byte
MB0
MB1
MB2
MB3
MB4
MB5
Request
7
6
5
4
2
2
2
2
0x40
T
0x04
No. of table entry with target position
Reserved
Reserved
0:
Read out from position table.
1:
Read out from variables FILT1 ... FILT8.
Response
7
6
5
4
2
2
2
2
0x40
T
Return Code
0x04
Reserved
Reserved
Reserved
3
2
1
0
2
2
2
2
-
SRC
3
2
1
0
2
2
2
2
WAGO-I/O-SYSTEM 750
I/O Modules

Advertisement

Table of Contents
loading