Crank Disconnect Conditions Selection - Smartgen HGMS62 User Manual

Table of Contents

Advertisement

No.
Items
Level (Fuel Level)
3
Sensor
NOTE: The connected input signal of pressure sensor and aux. sensor 1 can be resistance, current or voltage. When
set "Custom Current/Voltage Curve" via controller panel, X coordinate data should expand 10 times, like 4mA input data
is "40".
8.5

CRANK DISCONNECT CONDITIONS SELECTION

No.
0
Frequency
1
Speed
2
Speed + Frequency
3
Oil pressure
4
Oil pressure + Frequency
5
Oil pressure + Speed
6
Oil pressure + Speed + Frequency
NOTE:
a) There are 3 kinds of crank disconnect conditions. Speed, frequency and oil pressure can be used alone. Oil pressure
is used with speed and generator frequency together is recommended, in order to make the starter and the engine
disconnect as soon as possible.
b) Speed sensor is a magnetic device installed on the engine body to test the number of flywheel teeth.
c) When choosing speed, ensure the number of flywheel teeth is the same as the preset, otherwise over or under speed
shutdown may occur.
d) If generator has no magnetic pickup sensor, don't choose speed item; otherwise Fail to Start or Loss of Speed Signal
shutdown will occur.
e) If the generator has no oil pressure sensor, don't choose corresponding item.
f)
If generator frequency has not been selected, controller will not measure and display the relative parameters (can be
applied to the pump set); if speed has not been selected, the rotating speed will be calculated by the generating
signal.
HGMS62 Split Type Genset Controller User Manual
Content
12-14 Reserved
15 Digital Input Port 6
0 Not used
1 Use-defined Resistance Curve
2 User-defined Current/Voltage Curve
3 SGD
4 SGH
5 SUZUKI
6-14 Reserved
15 Digital Input Port 7
Table 17 – Crank Disconnect Conditions Selection
Defined input resistance range is
0Ω~6000Ω, factory default is
SGH sensor.
Content
Description
Page 44 of 58