Leuze electronic CML 720i Ex Operating Instructions Manual page 73

Measuring light curtain
Table of Contents

Advertisement

Parameter
Trigger Settings
Cascading
Function type
Trigger delay time →
Start measurement
Master cycle time
Blanking settings (group 8)
Up to four beam areas can be deactivated. Deactivated beams can be assigned the logical
values 0, 1 or the value of the adjacent beam. With auto blanking activated, up to four beam
areas are automatically suppressed during teaching.
Auto blanking should only be activated during commissioning of the CML 700i to suppress inter-
fering objects. In process mode, auto blanking should be deactivated.
For details on this topic see chapter 11.4.
NOTICE
Perform teach after changing the blanking configuration!
 Perform a teach after changing the blanking configuration.
A teach can be performed via the receiver control panel or via the teach command.
Parameter
Blanking settings
Number of auto-blanking
areas
Auto blanking (during
teaching)
Logical value for blanking
area 1
Leuze electronic
Index
Sub-
Data type
index
73
0
record 64 bit,
isolated
access to
sub-index not
possible
73
1
unsigned 8
(bit
offset
= 56)
73
2
unsigned 8
(bit
offset
= 48)
73
3
unsigned 16
(bit
offset
= 32)
73
5
unsigned 16
(bit
offset
= 0)
Index
Sub-
Data type
index
76
0
record
208 bit, iso-
lated access
to sub-index
not possible
76
1
unsigned 8
(bit
offset
= 200)
76
2
unsigned 8
(bit
offset
= 192)
76
3
unsigned 16
(bit
offset
= 176)
Starting up the device - IO-Link interface
Access
Value range
Default Explanation
RW
RW
0 ... 1
0
RW
0 ... 1
0
RW
500 ... 65535
500
RW
1 ... 6500
1
Access
Value range
Default Explanation
RW
RW
0 ... 4
0
RW
0 ... 1
0
RW
0 ... 4
0
CML 720i Ex
0: Not active (constant measurement of the sen-
sor)
1: Active (sensor expects trigger signal)
0: Slave (expects trigger signal)
1: Master (sends trigger signal)
Unit: µs
Unit: ms
Permissible number of auto-blanking areas
0: 0 auto-blanking areas
1: 1 auto-blanking area
2: 2 auto-blanking areas
3: 3 auto-blanking areas
4: 4 auto-blanking areas
0: Not active (manual blanking area configuration)
1: Active (automatic area configuration through
teach)
0: No beams blanked
1: Logical value 0 for blanked beams
2: Logical value 1 for blanked beams
3: Logical value = same as adjacent beam with
lower beam number
4: Logical value = same as adjacent beam with
higher beam number
73