Power-Up Teach - Leuze electronic CML 720i Ex Operating Instructions Manual

Measuring light curtain
Table of Contents

Advertisement

Auto blanking cannot be used to detect transparent objects.
Deactivated beams are lost if the beam mode is changed while auto blanking is active.
NOTICE
Deactivate auto blanking in process mode!
 Deactivate auto blanking in process mode.
Activate auto blanking only during commissioning of the device to suppress distracting objects.
NOTICE
Deactivate auto blanking during Power-Up Teach!
 Deactivate auto blanking if "Power-Up Teach" is activated (see chapter 4.7).
NOTICE
Resetting all blanking areas!
 To deactivate blanking areas, leave auto blanking active with at least the same number of blanking
areas.
Perform a new teach in a free measurement field.
 To deactivate blanking with the
ing areas as zero and, at the same time, deactivate each area.
Perform a new teach.
4.7

Power-Up Teach

After applying operating voltage, the "Power-Up Teach" function performs a teach event when the device
is ready for operation.
• If the Power-Up teach is successful, the new teach values are adopted if they are different from the
previously stored teach values.
• If the Power-Up teach is not successful (e.g. object in the light path), the previously saved teach val-
ues are used.
The "Power-Up Teach" event can only be activated via the receiver control panel.
NOTICE
Deactivate auto blanking during Power-Up Teach!
 Deactivate auto blanking if "Power-Up Teach" is activated.
NOTICE
No objects in the light path!
 During "Power-Up Teach", ensure that no beams are partially covered by an object.
4.8
Smoothing
With the smoothing function, interrupted beams are then only taken into account in the evaluation if the set
minimum number of adjacent beams is reached at the same time.
Smoothing can be used, e.g., to suppress interference caused by spot soiling of the lens cover.
Smoothing "1" means that every interrupted beam is evaluated.
Leuze electronic
Sensor Studio
configuration software, configure the number of blank-
CML 720i Ex
Functions
29

Hide quick links:

Advertisement

Table of Contents
loading