4.10 S7 TESTING
PATH: SETPOINTS MMMMMMM S7 TESTING MMMMMM SWITCH INPUTS SIMULATION
SIMULATION:
OFF
MESSAGE
4
SIMULATION ENABLED
MESSAGE
FOR:
15 min
START A
MESSAGE
INPUT: OPEN
START B
MESSAGE
INPUT: OPEN
STOP
MESSAGE
INPUT: OPEN
CONTACTOR A STATUS
MESSAGE
INPUT:OPEN
CONTACTOR B STATUS
MESSAGE
INPUT: OPEN
LOCAL ISOLATOR
MESSAGE
INPUT: OPEN
4-44
Range: ON, OFF
Enter ON to switch from actual switch inputs to the programmed
simulation status of each switch input. While simulation is on the actual
switch input status will be overridden by the simulated status of each
input. Set this setpoint to OFF after simulation is complete. As a
safeguard, simulation will automatically turn off if:
power to the MM3 is turned off and on
the time programmed in S7: TESTING\SWITCH INPUTS SIMULATION\SIM-
ULATION ENABLED FOR has elapsed since simulation was first enabled
When switch inputs simulation is turned on the following flash message
will be displayed for 3 seconds.
CURRENT SIMULATION
HAS BEEN ENABLED
When switch inputs is turned off the following flash message will be dis-
played for 3 seconds.
CURRENT SIMULATION
HAS BEEN DISABLED
Range: 5 to 300 min. or UNLIMITED; Step: 5
Select the length of time that simulation is enabled. When this time has
elapsed, switch inputs simulation will turn off. If UNLIMITED is selected,
simulated switch input status will be used until simulation is turned off via
the SIMULATION ON/OFF setpoint, via the serial port, or until control power
is removed.
Range: OPEN, CLOSED
Enter the status of this switch input as OPEN or CLOSED. The functionality
of this input remains as is with actual input connected.
Range: OPEN, CLOSED
Enter the status of this switch input as OPEN or CLOSED. The functionality
of this input remains as is with actual input connected.
Range: OPEN, CLOSED
Enter the status of this switch input as OPEN or CLOSED. The functionality
of this input remains as is with actual input connected.
Range: OPEN, CLOSED
Enter the status of this switch input as OPEN or CLOSED. The functionality
of this input remains as is with actual input connected.
Range: OPEN, CLOSED
Enter the status of this switch input as OPEN or CLOSED. The functionality
of this input remains as is with actual input connected.
Range: OPEN, CLOSED
Enter the status of this switch input as OPEN or CLOSED. The functionality
of this input remains as is with actual input connected.
MM3 Motor Manager 3
4 SETPOINTS

4.10.7 SWITCH INPUTS SIMULATION