APPENDIX A MM3 COMMISSIONING SUMMARYA.1 COMMISIONING SUMMARY
The following table lists all of the MM3 setpoints. Your application of the MM3 may not use all of them.
Table A–1: MM3 COMMISSIONING (Sheet 1 of 8)
DESCRIPTION
S1: SYSTEM CONFIGURATION
COMMUNICATIONS
Communications Address
Baud Rate
Parity
MOTOR IDENTIFICATION
Motor Name
Motor Rating
High Speed Motor Rating
System Supply
STARTER
Starter Type
Change Over Current
Change Over Time
Transfer Time
High Speed Start Block
Ramp Up Time
Ramp Down Time
Stage One Shorting Time
Contactor Sequence
Change Over Time (Autotrans)
Starts Per Hour
CT/VT INPUTS
Phase CT Primary Amps
High Speed Phase CT Primary Amps
Ground Fault CT Inputs
VT Primary Voltage
VT Connection Type
VT Secondary Voltage
Nominal Frequency
THERMISTOR
Cold Resistance
GE Power Management
DEFAULT
USER VALUE
Off
9600
None
Motor
Off
Off
480 V
Off
1.5 x FLC
30 sec.
10 sec.
Disable
5 sec.
5 sec.
5 sec.
1S-2S
5 sec.
5
100 A
100 A
50:0.025 CBCT
Off
Phase (A-N)
120 V
60 Hz
0.1 KΩ
MM3 Motor Manager 3
A.1 COMMISIONING SUMMARY
Table A–1: MM3 COMMISSIONING (Sheet 2 of 8)
DESCRIPTION
Hot Resistance
Thermistor Trip
Thermistor Alarm
FAULT MODE
Internal Fault Trip
Serial Comms Failure Trip
Serial Comms Failure Alarm
Change Command Mode on Alarm
PROGRAMMABLE MESSAGE
Programmable Message
PREFERENCES
Default Message Display
Default Message Brightness
S2: PROTECTION
MOTOR PROTECTION – THERMAL
Full Load Current
High Speed Full Load Current
Overload Pickup Level
Overload Curve Number
Hot/Cold Curve Ratio
MOTOR PROTECTION – GROUND FAULT
Ground Fault Alarm Level
Ground Fault Alarm Delay On Run
Ground Fault Alarm Delay On Start
Ground Fault Trip Level
Ground Fault Trip Delay On Run
Ground Fault Trip Delay On Start
MOTOR PROTECTION – OPTIONS
Minimize Reset Time
Stopped Motor Cool Time
Overload Trip Reset
Reset Lockout Using Reset Key

A.1.1 DESCRIPTION

A
DEFAULT
USER VALUE
5.0 KΩ
Disable
Disable
Enable
Off
Off
Disable
Sample Text
10 sec.
60%
100 A
100 A
1.00 x FLA
4
75%
Off
10 sec.
10 sec.
Off
1.0 sec.
1.0 sec.
Enable
30 min.
Manual
Enable