8.5 CHASSIS MOUNT UNITS
8.5 CHASSIS MOUNT UNITS
MM3 chassis mount units no longer support automatic baud rate linking. The default communication settings
are 9600 baud, 8 data bits, one stop bit, no parity. It is necessary to initially communicate with these settings
and change them one at a time. After each change the master must be changed to match the communication
setting change in the MM3.
1. Assume your system communicates at 19200 baud and even parity.
2. Use MM3PC to establish communications with the chassis mount MM3 at 9600 baud and no parity.
3. Select the Communication > Set Slave Address menu item and follow the on screen instructions to store
the communication address of the MM3. When completed, select OK to exit.
4. Select the Communication > Troubleshooting menu. This opens the Memory Map Inspection window
shown below: