6.6 DATA FORMATS
Table 6–13:
MODBUS DATA FORMATS (Sheet 7 of 13)
CODE
DESCRIPTION
F26
Unsigned Integer: Relay / LED Test Data
0 = Normal operation mode
1 = Contactor A On
2 = Contactor B On
3 = AUX Relay 1 On
4 = AUX Relay 2 On
5 = All Relays On
6 = Running LED On
7 = Stopped LED On
8 = Tripped LED On
9 = Alarm LED On
10 = Fault LED On
11 = Auto LED On
12 = Manual LED On
13 = All LEDs On
14 = Flash Voltage On
F27
Unsigned Integer: Auto Mode Definition
0 = Serial
1 = Hard-Wired
F28
Unsigned Integer: Overload Curve
1 = Curve # 1
2 = Curve # 2
3 = Curve # 3
4 = Curve # 4
6
5 = Curve # 5
6 = Curve # 6
7 = Curve # 7
8 = Curve # 8
9 = NEMA Class 10
10 = NEMA Class 15
11 = NEMA Class 20
12 = NEMA Class 30
F29
Unsigned Integer: ESD Indication
0 = OFF when healthy
1 = ON when healthy
F30
Unsigned Integer:
Normally Open / Normally Closed
0 = N.O.
1 = N.C.
F31
Parity Type
0 = NONE
1 = EVEN
2 = ODD
F32
Contactor Sequence
0 = 1S-2S
1 = 2S-1S
6-40
Table 6–13:
MODBUS DATA FORMATS (Sheet 8 of 13)
BITMASK
CODE
DESCRIPTION
FFFF
F33
Manufacture Month/Day
---
Month: 1 = January, 2 = February...
12 = December
---
Day: 1 to 31 in steps of 1
---
F34
Manufacture Year: Unsigned Integer
---
Year: 1995, 1996
---
F35
Unsigned Integer: CT Connection Type
---
0 = 3 CTs
---
1 = 2 CTs (A and C)
---
F36
Simulated Switch State
---
0 = OPEN
---
1 = CLOSED
---
F37
Unsigned Integer: On / Off
---
0 = Off
---
1 = On
---
F100
Switch Input Status:
---
Interlock Input 1
FFFF
Interlock Input 2
---
Interlock Input 3
---
Interlock Input 4
FFFF
Interlock Input 5
---
Interlock Input 6
---
Interlock Input 7
---
Interlock Input 8
---
Interlock Input 9
---
Interlock Input 10
---
Stop
---
Start A
---
Start B
---
Local Isolator N/O
---
Contactor A N/O
---
Contactor B N/O
---
F101
LED Status Flags 1
FFFF
Running
---
Stopped
---
Tripped
FFFF
Alarm
---
Fault
---
Test 1
FFFF
Test 2
---
Not Used
---
Not Used
---
Not Used
FFFF
Not Used
---
Not Used
---
Not Used
MM3 Motor Manager 3
6 COMMUNICATIONS
BITMASK
FFFF
---
---
FFFF
---
FFFF
---
---
FFFF
---
---
FFFF
---
---
FFFF
0001
0002
0004
0008
0010
0020
0040
0080
0100
0200
0400
0800
1000
2000
4000
8000
FFFF
0001
0002
0004
0008
0010
0020
0040
0080
0100
0200
0400
0800
1000
GE Power Management