4 SETPOINTS

4.2 S1 CONFIGURATION

]] SETPOINTS
]] S1: CONFIGURATION
This page is used to enter all information about the MM3 configuration and the motor being protected. Set-
points page 1 is divided into eight sections: COMMUNICATIONS, MOTOR IDENTIFICATION, STARTER, CT /
VT INPUTS, THERMISTOR, FAULT MODE, STATISTICS, PROGRAMMABLE MESSAGES, and PREFER-
ENCES.
]] SETPOINTS
]] S1: CONFIGURATION
PATH: SETPOINTS M S1: CONFIGURATION M COMMUNICATIONS

COMMUNICATIONS

ADDRESS:
OFF
MESSAGE
BAUD RATE:
9600
MESSAGE
PARITY: NONE
MESSAGE
GE Power Management
] COMMUNICATIONS
MESSAGE
]
] MOTOR
MESSAGE
] IDENTIFICATION
] STARTER
MESSAGE
]
] CT/VT INPUTS
MESSAGE
]
] THERMISTOR
MESSAGE
]
] FAULT MODE
MESSAGE
]
] STATISTICS
MESSAGE
]
] PROGRAMMABLE
MESSAGE
] MESSAGES
] PREFERENCES
]
MESSAGE
Range: 1 to 255 or OFF, Step: 1
Each MM3 on the same serial communication network must have a
unique address in the range of 1 to 255. Computer software driving the
serial network must be configured to recognize each separate address.
Range: 1200, 2400, 4800, 9600, 19200, 57600
Selects the data transfer rate for Modbus serial communications.
Range: NONE, ODD, EVEN
This setpoint determines what type of parity checking is used when
communicating to the MM3.
MM3 Motor Manager 3
4.2 S1 CONFIGURATION

4.2.1 DESCRIPTION

4.2.2 COMMUNICATIONS
4-3