6.5 MEMORY MAP
Table 6–12: MODBUS MEMORY MAP (Sheet 5 of 19)
GROUP
MODICON
USER
30257
DEFINABLE
30258
DATA
30259
30260
30261
30262
30263
30264
30265
30266
30267
30268
30269
30270
30271
30272
↓
30376
Setpoint Values (Holding Registers) Addresses - 1000-1FFF
MOTOR
44097
ID
44098
44099
44100
6
44101
44102
44103
44104
44105
44106
44107
44108
44109
44110
44111
44112
STARTER
44113
44114
44115
44116
44117
44118
44119
Notes:
* – Maximum setpoint value and 65535 represent OFF
** – 1/Phase Current Scale Factor x A
*** – 101 represents unlimited
† – Minimum setpoint value represents OFF
~* – 0.1 x A when Hi resolution mode is disabled; 0.01 x A when enabled
6-22
REGISTER
ADDRESS
DESCRIPTION
DEC
HEX
256
0100
User Definable Data 0000
257
0101
User Definable Data 0001
258
0102
User Definable Data 0002
259
0103
User Definable Data 0003
260
0104
User Definable Data 0004
261
0105
User Definable Data 0005
262
0106
User Definable Data 0006
263
0107
User Definable Data 0007
264
0108
User Definable Data 0008
265
0109
User Definable Data 0009
266
010A
User Definable Data 000A
267
010B
User Definable Data 000B
268
010C User Definable Data 000C
269
010D User Definable Data 000D
270
010E
User Definable Data 000E
271
010F
User Definable Data 000F
↓
↓
375
0177
User Definable Data 0077
4096
1000
Motor Name characters 1 and 2
4097
1001
Motor Name characters 3 and 4
4098
1002
Motor Name characters 5 and 6
4099
1003
Motor Name characters 7 and 8
4100
1004
Motor Name characters 9 and 10
4101
1005
Motor Name characters 11 and 12
4102
1006
Motor Name characters 13 and 14
4103
1007
Motor Name characters 15 and 16
4104
1008
Motor Name characters 17 and 18
4105
1009
Motor Name characters 19 and 20
4106
100A
Motor Power Rating
4107
100B
High Speed Motor Power Rating
4108
100C System Supply Voltage
4109
100D ...Reserved...
4110
100E
...Reserved...
4111
100F
...Reserved...
4112
1010
Starter Type
4113
1011
Change-over Current
4114
1012
Change-over Time
4115
1013
Transfer Time
4116
1014
Ramp Up Time
4117
1015
Ramp Down Time
4118
1016
Stage One Shorting Time
MM3 Motor Manager 3
REGISTER
VALUE
RANGE
↓
↓
32-127
32-127
32-127
32-127
32-127
32-127
32-127
32-127
32-127
32-127
3-11001
3-11001
110-600
...
...
...
0-11
10-51
1-100
1-125
1-125
1-125
1-125
6 COMMUNICATIONS
FACTORY
STEP
UNITS
FOR-
DEFAULT
VALUE
AND
MAT
VALUE
SCALE
(CONVERTED)
↓
↓
↓
1
ASCII
F10
1
ASCII
F10
1
ASCII
F10
1
ASCII
F10
1
ASCII
F10
1
ASCII
F10
1
ASCII
F10
1
ASCII
F10
1
ASCII
F10
1
ASCII
F10
1
0.1 xkW
F1*
65535 = OFF
1
0.1 xkW
F1*
65535 = OFF
1
V
F1
...
...
...
...
...
...
...
...
...
1
---
F11
0 = OFF
1
0.1 xFLC
F1*
15 = 1.5 xFLC
1
s
F1
1
s
F1
1
s
F1
1
s
F1
1
s
F1
GE Power Management
↓
"MO"
"TO"
"R "
" "
" "
" "
" "
" "
" "
" "
480
...
...
...
30
10
5
5
5
Need help?