6.5 MEMORY MAP
Table 6–12: MODBUS MEMORY MAP (Sheet 7 of 19)
GROUP
MODICON
MOTOR
44161
PROTECTION
44162
GROUND
44163
44164
44165
44166
44167
44168
44169
MOTOR
44170
PROTECTION
44171
OPTIONS
44172
44173
44174
44175
44176
LOAD
44177
PROTECTION
44178
44179
44180
44181
44182
44183
6
44184
44185
44186
44187
44188
44189
44190
44191
44192
CONFIG.
44193
INPUTS
44194
44195
44196
44197
44198
44199
44200
44201
44202
Notes:
* – Maximum setpoint value and 65535 represent OFF
** – 1/Phase Current Scale Factor x A
*** – 101 represents unlimited
† – Minimum setpoint value represents OFF
~* – 0.1 x A when Hi resolution mode is disabled; 0.01 x A when enabled
6-24
REGISTER
ADDRESS
DESCRIPTION
DEC
HEX
4160
1040
Ground Fault Alarm Level (residual)
4161
1041
Ground Fault Alarm Level (50:0.025 CT)
4162
1042
Ground Fault Alarm Delay on Run
4163
1043
Ground Fault Trip Level (residual)
4164
1044
Ground Fault Trip Level (50:0.025 CT)
4165
1045
Ground Fault Trip Delay on Run
4166
1046
Delay Contactor Ground Fault Trip By (Aux1)
4167
1047
Delay Contactor Ground Fault Trip By (Aux2)
4168
1048
...Reserved...
4169
1049
Minimize Reset Time
4170
104A
Stopped Motor Cooling Time
4171
104B Overload Trip Reset
4172
104C Phase Unbalance Alarm
4173
104D Thermal Capacity Alarm
4174
104E
Open Control Circuit Trip
4175
104F
Reset Alarms using the Reset Key
4176
1050
Under Power Alarm Level
4177
1051
Under Power Alarm Delay
4178
1052
Under Power Trip Level
4179
1053
Under Power Trip Delay
4180
1054
Acceleration Time Alarm Delay
4181
1055
Acceleration Time Trip Delay
4182
1056
Load Increase Alarm Level
4183
1057
Undercurrent Alarm Level
4184
1058
Undercurrent Alarm Delay
4185
1059
Undercurrent Trip Level
4186
105A
Undercurrent Trip Delay
4187
105B
Stalled Rotor Trip Level
4188
105C Stalled Rotor Trip Delay
4189
105D ...Reserved...
4190
105E
...Reserved...
4191
105F
...Reserved...
4192
1060
Interlock Input 1 Function
4193
1061
Startup Override Delay
4194
1062
Running Override Delay
4195
1063
Operation
4196
1064
Instantaneous Alarm
4197
1065
...Reserved...
4198
1066
...Reserved...
4199
1067
...Reserved...
4200
1068
Interlock Input 2 Function
4201
1069
Startup Override Delay
MM3 Motor Manager 3
6 COMMUNICATIONS
REGISTER
STEP
UNITS
FOR-
VALUE
VALUE
AND
MAT
RANGE
SCALE
10-101
1
% of FLC
F1*
1-151
1
0.1 x A
F1*
1-60
1
s
F1
10-101
1
% of FLC
F1*
0-151
1
0.1 x A
F1*
0-50
1
0.1 x s
F1
0-1000
100
ms
F1
0-1000
100
ms
F1
...
...
...
...
0-1
1
---
F14
5-1080
1
minutes
F1
0-1
1
---
F16
0-1
1
---
F14
1-101
1
%
F1*
0-1
1
---
F14
0-1
1
---
F14
2-11001
1
0.1 xkW
F1*
1-60
1
s
F1
2-11001
1
0.1 xkW
F1*
1-60
1
s
F1
5-1255
5
0.1 x s
F1*
5-1255
5
0.1 x s
F1*
10-131
1
% FLC
F1*
10-101
1
% FLC
F1*
1-60
1
s
F1
10-101
1
% FLC
F1*
1-60
1
s
F1
115-455
5
0.01 x FLC
F1*
5-50
5
0.1 x s
F1
...
...
...
...
...
...
...
...
...
...
...
...
0-34
1
---
F17
0-3601
1
s
F1*
0-3601
1
s
F1*
0-1
1
---
F18
0-1
1
---
F14
...
...
...
...
...
...
...
...
...
...
...
...
0-34
1
---
F17
0-3601
1
s
F1*
GE Power Management
FACTORY
DEFAULT
VALUE
(CONVERTED)
65535 = OFF
65535 = OFF
10
65535 = OFF
65535 = OFF
10 = 1.0
0
0
...
1 = ENABLE
30
0 = MANUAL
1 = ENABLE
101 = OFF
0 = Disable
0 = Disable
65535 = OFF
10
65535 = OFF
10
65535 = OFF
65535 = OFF
65535 = OFF
65535 = OFF
10
65535 = OFF
10
450 = 4.50 x FLC
30 = 3.0 s
...
...
...
0 = NOT USED
0
0
0 = IL STOP
0 = DISABLE
...
...
...
0 = NOT USED
0
Need help?
Do you have a question about the MM3 and is the answer not in the manual?