Motor Status - GE MM3 Instruction Manual

Motor manager 3
Hide thumbs Also See for MM3:
Table of Contents

Advertisement

5.4 A2 STATUS
PATH: ACTUAL VALUES MM A2: STATUS MMM MOTOR STATUS

MOTOR STATUS:

RUNNING
MESSAGE
DELAYED RESTART IN
MESSAGE
PROGRESS:
DELAYED START IN
MESSAGE
PROGRESS:
TRANSFER TIME IN
MESSAGE
PROGRESS:
RESTART INHIBIT
MESSAGE
25 s
EXTERNAL START
5
MESSAGE
CAUSE OF STOP
MESSAGE
CAUSE OF LAST STOP
MESSAGE
EXTERNAL STOP
MESSAGE
5-8
This message has the same possible values as the Motor Status
message in page A1: DATA \ MOTOR DATA.
This message will appear if a delayed undervoltage restart is in progress.
The displayed time indicates the time remaining until the start sequence
15 s
will begin.
This message will appear if a delayed start is in progress. This occurs if
one of the auxiliary relays is set to Pre Contactor A OR B operation. The
15 s
displayed time indicates the time remaining until contactor A energizes.
This message will appear if a high speed to low speed transition is
occurring on a Two Speed starter or if a direction change is occurring on
10 s
Reversing starter. The displayed time indicates either the time remaining
until the low speed output relay (Contactor A) will energize, or the time
remaining until the forward output relay (Contactor A) or the reverse
output relay (Contactor B) will energize.
This message will appear when an autotransformer start is inhibited. The
restart inhibit time is determined from the autotransformer starts per hour
setpoint.
This message will appear if the contactor closed without receiving a start
command from the MM3. The MM3 will close the corresponding output
relay to seal in the contactor.
This message will appear to indicate the cause of the current stop
condition.
This message indicates the cause of the last stop operation.
This message indicates that the stop operation was caused externally to
the MM3. i.e. The contactor coil de-energized
MM3 Motor Manager 3
5 ACTUAL VALUES
5.4.4 MOTOR STATUS
GE Power Management

Advertisement

Table of Contents
loading

This manual is also suitable for:

Motor manager 3

Table of Contents