Download Print this page

Standard Ao - ABB ACS380 Firmware Manual

Machinery control program
Hide thumbs Also See for ACS380:

Advertisement

ACS380 FW.book Page 146 Friday, May 4, 2018 4:18 PM
146 Parameters
No.
Name/Value
13

13 Standard AO

13.02
AO force selection
Bit
Value
0
1 = Force AO1 to value of parameter
1...15
Reserved.
0000h...FFFFh
13.11
AO1 actual value
0.000...22.000 mA
13.12
AO1 source
Zero
Motor speed used
Output frequency
Motor current
Motor current % of
motor nom
Motor torque
DC voltage
Output power
Speed ref ramp in
Speed ref ramp out
Speed ref used
Freq ref used
Process PID out
Temp sensor 1
excitation
Temp sensor 2
excitation
Abs motor speed used
Abs motor speed %
Abs output frequency
Abs motor torque
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Configuration of standard analog outputs.
Selects the analog outputs that will be forced to values
defined by parameters.
The true source signals of the analog outputs can be
overridden for eg. testing purposes. A forced value
parameter is provided for each analog output, and its
value is applied whenever the corresponding bit in this
parameter is 1.
Note: Boot and power cycle reset the force selections
(parameters
13.02
and 13.11).
13.13 AO1 forced
Forced values selector for analog output AO1.
Displays the value of AO1 in mA.
This parameter is read-only.
Value of AO1.
Selects a signal to be connected to analog output AO1.
None.
01.01 Motor speed used
01.06 Output frequency
01.07 Motor current
01.08 Motor current % of motor nom
01.10 Motor torque
01.11 DC voltage
01.14 Output power
23.01 Speed ref ramp
input.
23.02 Speed ref ramp output
24.01 Used speed reference
28.02 Frequency ref ramp output
40.01 Process PID output actual
The output is used to feed an excitation current to the
temperature sensor 1, see parameter
1
source. See also section
Motor thermal
The output is used to feed an excitation current to the
temperature sensor 2, see parameter
2
source. See section
Motor thermal protection
Program
features.
01.61 Abs motor speed used
01.62 Abs motor speed %
01.63 Abs output frequency
01.64 Abs motor torque
Default
FbEq 16
0000h
value.
1 = 1
-
1 = 1 mA
Output
frequency
0
1
3
4
5
6
7
8
10
11
12
14
16
20
35.11 Temperature
protection.
21
35.21 Temperature
in chapter
26
27
28
30

Hide quick links:

Advertisement

loading