Encoder 1 Configuration - ABB ACS380 Firmware Manual

Machinery control program
Hide thumbs Also See for ACS380:

Advertisement

ACS380 FW.book Page 329 Friday, May 4, 2018 4:18 PM
No.
Name/Value
Done
Refresh
92
92 Encoder 1
configuration
92.10
Pulses/revolution
0...65535
95
95 HW configuration
95.01
Supply voltage
Automatic / not
selected
208...240 V
380...480 V
95.02
Adaptive voltage limits
Disable
Enable
95.03
Estimated AC supply
voltage
0.0...65535.0 V
95.04
Control board supply
Internal 24V
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
The refreshing is completed.
Refresh function is running.
Settings for encoder 1.
Notes:
• The contents of the parameter group vary according to
the selected encoder type.
• It is recommended that encoder connection 1 (this
group) is used whenever possible.
(Visible when a TTL, TTL + HTL encoder is selected)
Defines the pulse number per revolution.
Number of pulses.
Various hardware-related settings.
Selects the supply voltage range. This parameter is used
by the drive to determine the nominal voltage of the supply
network. The parameter also affects the current ratings
and the DC voltage control functions (trip and brake
chopper activation limits) of the drive.
WARNING! An incorrect setting may cause the
motor to rush uncontrollably, or the brake chopper
or resistor to overload.
Note: The selections shown depend on the hardware of
the drive. If only one voltage range is valid for the drive in
question, it is selected by default.
No voltage range selected. The drive will not start
modulating before a range is selected, unless parameter
95.02 Adaptive voltage limits
is set to Enable, in which
case the drive estimates the supply voltage itself.
200...240 V, available for ACS380-04-xxxx-1/-2 drives
380...480 V, available for ACS380-04-xxxx-4 drives
Enables adaptive voltage limits.
Adaptive voltage limits can be used if, for example, an
IGBT supply unit is used to raise the DC voltage level. If
the communication between the inverter and IGBT supply
unit is active, the voltage limits are related to the DC
voltage reference from the IGBT supply unit. Otherwise
the limits are calculated based on the measured DC
voltage at the end of the pre-charging sequence.
This function is also useful if the AC supply voltage to the
drive is high, as the warning levels are raised accordingly.
Adaptive voltage limits disabled.
Adaptive voltage limits enabled.
AC supply voltage estimated by calculation. Estimation is
done every time the drive is powered up and is based on
the rise speed of voltage level of the DC bus while the
drive charges the DC bus.
Voltage.
Specifies how the control board of the drive is powered.
The drive control board is powered from the drive power
unit it is connected to.
Parameters
329
Default
FbEq 16
0
1
2048
-
Automatic /
not selected
0
1
2
Enable
0
1
-
10 = 1 V
Internal 24V
0