ACS380 FW.book Page 320 Friday, May 4, 2018 4:18 PM
320 Parameters
No.
Name/Value
58.122 RPDO21 word 2
58.123 RPDO21 word 3
58.124 RPDO21 word 4
71

71 External PID1

71.01
External PID act value
71.02
Feedback act value
71.03
Setpoint act value
71.04
Deviation act value
71.06
PID status word
Bit
Name
0
PID active
1
Reserved
2
Output frozen
3...6
Reserved
7
Output limit high
8
Output limit low
9
Deadband active
10...11 Reserved
12
Internal setpoint
active
13...15 Reserved
0000h...FFFFh
71.07
PID operation mode
71.08
Feedback 1 source
71.11
Feedback filter time
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Selects a parameter that is mapped to RPDO21 word 2.
For selections, see parameter
58.101 TPDO1 word
Note: If parameter
58.01
= [1] Modbus RTU, this
parameter is hidden.
Selects a parameter that is mapped to RPDO21 word 3.
For selections, see parameter
58.101 TPDO1 word
Note: If parameter
58.01
= [1] Modbus RTU, this
parameter is hidden.
Selects a parameter that is mapped to RPDO21 word 4.
For selections, see parameter
58.101 TPDO1 word
Note: If parameter
58.01
= [1] Modbus RTU, this
parameter is hidden.
Configuration of external PID.
See parameter
40.01 Process PID output
See parameter
40.02 Process PID feedback
See parameter
40.03 Process PID setpoint
See parameter
40.04 Process PID deviation
Displays status information on process external PID
control.
This parameter is read-only.
Value
1 = Process PID control active.
1 = Process PID controller output frozen. Bit is set if parameter
71.38 Output freeze enable
is TRUE, or the deadband function is
active (bit 9 is set).
1 = PID output is being limited by par. 40.37.
1 = PID output is being limited by par. 40.36.
1 = Deadband is active.
1 = Internal setpoint active (see par. 40.16...40.16)
Process PID control status word.
See parameter
40.07 Process PID operation
See parameter
40.08 Set 1 feedback 1
See parameter
40.11 Set 1 feedback filter
Default
FbEq 16
None
1.
None
1.
None
1.
actual.
-
actual.
-
actual.
-
actual.
-
-
1 = 1
mode.
Off
source.
Not selected
time.
0.000 s