ACS380 FW.book Page 53 Friday, May 4, 2018 4:18 PM

External control

When the drive is in external control, control commands are given through:
• the I/O terminals (digital and analog inputs)
• the fieldbus interface (via the embedded fieldbus interface or an optional fieldbus
adapter module)
• external panel (assistant panel).
Two external control locations, EXT1 and EXT2, are available. You can select the
sources of the start and stop commands separately for each location by setting
parameters 20.01...20.10. The operating mode can be selected separately for each
location, which enables quick switching between different operating modes, for
example speed and torque control. Selection between EXT1 and EXT2 is done via
any binary source such as a digital input or fieldbus control word by parameter
Ext1/Ext2
selection. You can also select the source of reference for each operating
mode separately, and the operation mode.
Settings
Parameters 20.01...
Block diagram: Run enable source for EXT1
The figure below shows the parameters that select the interface for run enable for
external control location EXT1.
0
1
DI1
DI0 2
Embedded fieldbus
Fieldbus adapter
Timed function
Supervision
A bit in a parameter
Settings
Parameters
19.11 Ext1/Ext2 selection
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
20.10
and
19.11 Ext1/Ext2 selection
Selected
DIO2
EFB MCW bit 3
FBA A MCW bit 3
Timed function
1...3
Supervision
1...6
Other [bit]
(page154) and 20.01...20.10.
Program features
(page154).
Select
Off
DI1
EXT1
Run enable
20.12
53
19.11