Process Pid Set 2 - ABB ACS380 Firmware Manual

Machinery control program
Hide thumbs Also See for ACS380:

Advertisement

ACS380 FW.book Page 273 Friday, May 4, 2018 4:18 PM
No.
Name/Value
Other
40.89
Set 1 setpoint
multiplier
-200000.00...
200000.00
40.90
Set 1 feedback
multiplier
-200000.00...
200000.00
40.91
Feedback data
storage
-327.68 ... 327.67
40.92
Setpoint data storage
-327.68 ... 327.67
40.96
Process PID output %
-100.00...100.00%
40.97
Process PID feedback
%
-100.00...100.00%
40.98
Process PID setpoint
%
-100.00...100.00%
40.99
Process PID deviation
%
-100.00...100.00%
41

41 Process PID set 2

41.08
Set 2 feedback 1
source
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Source selection (see
Terms and abbreviations
112).
Defines the multiplier with which the result of the function
specified by parameter
40.18 Set 1 setpoint function
multiplied.
Multiplier.
Defines the multiplier with which the result of the function
specified by parameter
40.10 Set 1 feedback function
multiplied.
Multiplier.
Storage parameter for receiving a process feedback value
eg. through the embedded fieldbus interface.
The value can be sent to the drive as Modbus I/O data.
Set the target selection parameter of that particular data
(58.101...58.114) to
Feedback data
storage. In
1 feedback 1 source
(or
40.09 Set 1 feedback 2
select
Feedback
storage.
Storage parameter for process feedback.
Storage parameter for receiving a process setpoint value
eg. through the embedded fieldbus interface.
The value can be sent to the drive as Modbus I/O data.
Set the target selection parameter of that particular data
(58.101...58.114) to
Setpoint data
storage. In
setpoint 1 source
(or
40.17 Set 1 setpoint 2
select
Setpoint data
storage.
Storage parameter for process setpoint.
Percentage scaled signal of parameter
feedback
actual.
Percentage.
Percentage scaled signal of parameter
feedback
actual.
Percentage.
Percentage scaled signal of parameter
setpoint
actual.
Percentage.
Percentage scaled signal of parameter
deviation
actual.
Percentage.
A second set of parameter values for process PID control.
The selection between this set and first set (parameter
group
40 Process PID set
1) is made by parameter
PID set1/set2
selection.
See also parameters 40.01...40.06, and the control chain
diagrams on pages
506
and 507.
See parameter
40.08 Set 1 feedback 1
Parameters
273
Default
FbEq 16
on page
-
1.00
is
1 = 1
1.00
is
1 = 1
0.00
40.08 Set
source),
100 = 1
0.00
40.16 Set 1
source),
100 = 1
40.01 Process PID
0.00%
100 = 1%
40.02 Process PID
0.00%
100 = 1%
40.03 Process PID
0.00%
100 = 1%
40.04 Process PID
0.00%
100 = 1%
40.57
source.
Not selected