No.
Name/Value
50.16
FBA A status word
00000000h...
FFFFFFFFh
50.17
FBA A actual value 1
-2147483648...
2147483647
50.18
FBA A actual value 2
-2147483648...
2147483647
51

51 FBA A settings

51.01
FBA A type
51.02
FBA A Par2
0...65535
...
...
51.26
FBA A Par26
0...65535
51.27
FBA A par refresh
Done
Configure
51.28
FBA A par table ver
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Displays the raw (unmodified) status word sent by fieldbus
adapter A to the master (PLC) if debugging is enabled by
parameter
50.12 FBA A debug
mode.
This parameter is read-only.
Status word sent by fieldbus adapter A to master.
Displays raw (unmodified) actual value ACT1 sent by
fieldbus adapter A to the master (PLC) if debugging is
enabled by parameter
50.12 FBA A debug
This parameter is read-only.
Raw ACT1 sent by fieldbus adapter A to master.
Displays raw (unmodified) actual value ACT2 sent by
fieldbus adapter A to the master (PLC) if debugging is
enabled by parameter
50.12 FBA A debug
This parameter is read-only.
Raw ACT2 sent by fieldbus adapter A to master.
Fieldbus adapter A configuration.
Displays the type of the connected fieldbus adapter
module.
0 = Module is not found or is not properly connected, or is
disabled by parameter
50.01 FBA A
enable; 0 = None;
1 = PROFIBUS DP; 32 = CANopen; 37 = DeviceNet;
128 = Ethernet; 132 = PROFINET IO; 135 = EtherCAT;
136 = ETH Pwrlink; 485 = RS-485 comm;
101 = ControlNet;
This parameter is read-only.
Parameters
51.02...51.26
are adapter module-specific.
For more information, see the documentation of the
fieldbus adapter module. Note that not all of these
parameters are necessarily in use.
Fieldbus adapter configuration parameter.
...
See parameter
51.02 FBA A
Par2.
Fieldbus adapter configuration parameter.
Validates any changed fieldbus adapter module
configuration settings. After refreshing, the value reverts
automatically to Done.
Note: This parameter cannot be changed while the drive
is running.
Refreshing done.
Refreshing.
Displays the parameter table revision of the fieldbus
adapter module mapping file (stored in the memory of the
drive).
In format axyz, where ax = major table revision number;
yz = minor table revision number.
This parameter is read-only.
Parameter table revision of adapter module.
Parameters
299
Default
FbEq 16
-
-
-
mode.
-
-
mode.
-
-
-
1 = 1
...
-
1 = 1
Done
0
1
-
-