ACS380 FW.book Page 120 Friday, May 4, 2018 4:18 PM
120 Parameters
No.
Name/Value

04.08

Active warning 3
0000h...FFFFh
04.11
Latest fault
0000h...FFFFh
04.12
2nd latest fault
0000h...FFFFh
04.13
3rd latest fault
0000h...FFFFh
04.16
Latest warning
0000h...FFFFh
04.17
2nd latest warning
0000h...FFFFh
04.18
3rd latest warning
0000h...FFFFh
05

05 Diagnostics

05.01
On-time counter
0...65535 d
05.02
Run-time counter
0...65535 d
05.03
Hours run
0.0...
429496729.5 h
05.04
Fan on-time counter
0...65535 d
05.10
Control board
temperature
-100... 300 °C or °F
05.11
Inverter temperature
-40.0...160.0%
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
3rd active warning in warning register.
Warning code.
Latest fault in the trip log store. The trip log store is loaded
with the active faults in the order they occur.
Fault code.
2nd fault in trip log store.
Fault code.
3rd fault in trip log store.
Fault code.
Latest warning in the warning log store. The warning log
store is loaded with the active warnings in the order they
occur.
Warning code.
2nd warning in trip log store.
Warning code.
3rd warning in trip log store.
Warning code.
Various run-time-type counters and measurements
related to drive maintenance.
All parameters in this group are read-only unless
otherwise noted.
Drive on-time counter. The counter runs when the drive is
powered.
On-time counter (number of days).
Motor run-time counter. The counter runs when the
inverter modulates.
Motor run-time counter.
Corresponding parameter to
05.02 Run-time counter
hours, that is, 24 *
05.02
value + fractional part of a day.
Hours.
Running time of the drive cooling fan. Can be reset from
the control panel by keeping Reset down for over 3
seconds.
Cooling fan run-time.
Measured temperature of the control board.
Temperature in degrees Celsius for Fahrenheit.
Estimated drive temperature in percent of fault limit. The
fault limit varies according to the type of the drive.
0.0% = 0 °C (32 °F)
100.0% = Fault limit
Temperature in percent.
Default
FbEq 16
-
1=1
-
1=1
-
1=1
-
1=1
-
1=1
-
1=1
-
1=1
-
1 = 1 d
-
1 = 1 d
in
-
10 = 1 h
-
1 = 1 d
-
1 = unit
-
1 = 1%